Energy Interaction among HVAC and Supermarket Environment
Commenced in January 2007
Frequency: Monthly
Edition: International
Paper Count: 33085
Energy Interaction among HVAC and Supermarket Environment

Authors: D. Woradechjumroen, H. Li, Y. Yu

Abstract:

Supermarkets are the most electricity-intensive type of commercial buildings. The unsuitable indoor environment of a supermarket provided by abnormal HVAC operations incurs waste energy consumption in refrigeration systems. This current study briefly describes significantly solid backgrounds and proposes easyto- use analysis terminology for investigating the impact of HVAC operations on refrigeration power consumption using the field-test data obtained from building automation system (BAS). With solid backgrounds and prior knowledge, expected energy interactions between HVAC and refrigeration systems are proposed through Pearson’s correlation analysis (R value) by considering correlations between equipment power consumption and dominantly independent variables (driving force conditions).The R value can be conveniently utilized to evaluate how strong relations between equipment operations and driving force parameters are. The calculated R values obtained from field data are compared to expected ranges of R values computed by energy interaction methodology. The comparisons can separate the operational conditions of equipment into faulty and normal conditions. This analysis can simply investigate the condition of equipment operations or building sensors because equipment could be abnormal conditions due to routine operations or faulty commissioning processes in field tests. With systematically solid and easy-to-use backgrounds of interactions provided in the present article, the procedures can be utilized as a tool to evaluate the proper commissioning and routine operations of HVAC and refrigeration systems to detect simple faults (e.g. sensors and driving force environment of refrigeration systems and equipment set-point) and optimize power consumption in supermarket buildings. Moreover, the analysis will be used to further study the FDD research for supermarkets in future.

Keywords: Energy interaction, HVAC, R-value, Supermarket buildings.

Digital Object Identifier (DOI): doi.org/10.5281/zenodo.1337543

Procedia APA BibTeX Chicago EndNote Harvard JSON MLA RIS XML ISO 690 PDF Downloads 3222

References:


[1] U.S. DOE, Office of Energy Efficiency and Renewable Energy Buildings Energy. 2010.
[2] N. Rivers, Management of Energy Usage in Supermarket Refrigeration Systems, The Institute of Refrigeration. Session 2004-2005.
[3] D. Kosar, O. Dumitrescu, "Humidity Effects on Supermarket Refrigerated Case Energy Performance: A Database Review". ASHRAE Transactions. Vol. 111 (1), 2005.
[4] R.H. Howell and P. Adams, Effects of Indoor Space Conditions on Refrigerated Display Case Performance, Final Report for ASHRAE Project No. 596RP, 1991.
[5] H. Henderson and M. Khattar, "Measured impacts of Humidity level on defrost performance and refrigerating system energy use", ASHRAE Transactions, vol. 109(1), 1999.
[6] R. Farmarzi, R. Sweetser and R. Henninger, Investigation of relative humidity impacts on the performance and energy use of refrigerated display cases, Final Report GRI- 00/0084. 2000.
[7] D.R. Felts and P. Bailey, The State of Affairs - Packaged Cooling Equipment in California, 2000.
[8] D. Woradechjumroen, Y. Yu, H. Li, H. Yang H and D. Yu, "Analysis of HVAC system oversizing in commercial buildings through field measurements", Energy and Buildings, 69, pp. 131-143, 2014.
[9] H. Henderson. The Impact of Part Load Air Conditioner Operation on Dehumidification Performance: Validating a Latent Capacity Degradation Model, Presented at IAQ & Energy. New Orleans, LA, Oct. 1998.
[10] Navigant Consulting, Inc. Energy Savings Potential and R&D Opportunities for Commercial Refrigeration. Energy Efficiency and Renewable Energy. Building Technologies Program. U.S. Department of Energy. September 23, 2009.
[11] R. Taylor. "Interpretation of the correlation coefficient: A basic review," Journal of Diagnostic Medical Sonography. vol. 6 (1), pp. 35-39, Jan. 1990.
[12] A.G. Asuero, A. Sayago and A.G. Gonzalez. "The correlation coefficient: An overview," Critical Reviews in Analytical Chemistry, vol. 36, pp. 41–59, 2006.
[13] I.P. Levin, Statistical Tests for Relationships: Correlation and Regression, In Relating Statistics and Experimental Design, 1999, pp. 33-34.