An Investigation to Study the Moisture Dependency of Ground Enhancement Compound
Authors: Arunima Shukla, Vikas Almadi, Devesh Jaiswal, Sunil Saini, Bhusan S. Patil
Abstract:
Lightning protection consists of three main parts; mainly air termination system, down conductor, and earth termination system. Earth termination system is the most important part as earth is the sink and source of charges. Therefore, even when the charges are captured and delivered to the ground, and an easy path is not provided to the charges, earth termination system would lead to problems. Soil has significantly different resistivities ranging from 10 Ωm for wet organic soil to 10000 Ωm for bedrock. Different methods have been discussed and used conventionally such as deep-ground-well method and altering the length of the rod. Those methods are not considered economical. Therefore, it was a general practice to use charcoal along with salt to reduce the soil resistivity. Bentonite is worldwide acceptable material, that had led our interest towards study of bentonite at first. It was concluded that bentonite is a clay which is non-corrosive, environment friendly. Whereas bentonite is suitable only when there is moisture present in the soil, as in the absence of moisture, cracks will appear on the surface which will provide an open passage to the air, resulting into increase in the resistivity. Furthermore, bentonite without moisture does not have enough bonding property, moisture retention, conductivity, and non-leachability. Therefore, bentonite was used along with the other backfill material to overcome the dependency of bentonite on moisture. Different experiments were performed to get the best ratio of bentonite and carbon backfill. It was concluded that properties will highly depend on the quantity of bentonite and carbon-based backfill material.
Keywords: Backfill material, bentonite, conducting soil, grounding material, low resistivity.
Procedia APA BibTeX Chicago EndNote Harvard JSON MLA RIS XML ISO 690 PDF Downloads 455References:
[1] S. C. Lim, C. Gomes, M. Z. A. A. Kadir, G. Nourirad, and Z. A. Malek, “Behaviour of backfill materials for electrical grounding systems under high voltage conditions,” J. Eng. Sci. Technol., vol. 10, no. 6, pp. 811–826, 2015.
[2] M. Kižlo and A. Kanbergs, “The Causes of the Parameters Changes of Soil Resistivity,” Sci. J. Riga Tech. Univ. Power Electr. Eng., vol. 25, no. 25, pp. 43–46, 2010, doi: 10.2478/v10144-009-0009-z.
[3] J. F. Tatum, “Ground Electrode Backfill Composition, Anode Bed and Apparatus,” 4,786,388, 1988.
[4] A. Azmi, N. A. Ahmad, L. K. Yiew, and Z. Abdul-Malek, “The use of enhancement material in grounding system: A review,” Indones. J. Electr. Eng. Comput. Sci., vol. 13, no. 2, pp. 453–460, 2019, doi: 10.11591/ijeecs.v13.i2.pp453-460.
[5] Z. Bin Burhanuddin, C. Gomes, A. Gomes, M. Z. K. Ab Kadir, W. F. Wan Ahmad, and N. Azis, “Characteristics of fulgurite-like structures under HV conditions: Effects on electrical earthing systems,” 33rd Int. Conf. Light. Prot. ICLP 2016, pp. 1–4, 2016, doi: 10.1109/ICLP.2016.7791435.
[6] H. Ş. Arel and E. Aydin, “Effects of Ca-, Mg-, K-, and Na-lignosulfonates on the behavior of fresh concrete,” Constr. Build. Mater., vol. 157, no. December, pp. 1084–1091, 2017, doi: 10.1016/j.conbuildmat.2017.09.190.
[7] A. Ghavamian, M. R. Maghami, S. Dehghan, and C. Gomes, “Concerns of corrosive effects with respect to lightning protection systems,” Eng. Fail. Anal., vol. 57, no. November, pp. 434–443, 2015, doi: 10.1016/j.engfailanal.2015.08.019.