Vibration Analysis of Power Lines with Moving Dampers
Commenced in January 2007
Frequency: Monthly
Edition: International
Paper Count: 84357
Vibration Analysis of Power Lines with Moving Dampers

Authors: Mohammad Bukhari, Oumar Barry

Abstract:

In order to reduce the Aeolian vibration of overhead transmission lines, the Stockbridge damper is usually attached. The efficiency of Stockbridge damper depends on its location on the conductor and its resonant frequencies. When the Stockbridge damper is located on a vibration node, it becomes inefficient. Hence, the static damper should be subrogated by a dynamic one. In the present study, a proposed dynamic absorber for transmission lines is studied. Hamilton’s principle is used to derive the governing equations, then the system of ordinary differential equations is solved numerically. Parametric studies are conducted to determine how certain parameters affect the performance of the absorber. The results demonstrate that replacing the static absorber by a dynamic one enhance the absorber performance for wider range of frequencies. The results also indicate that the maximum displacement decreases as the absorber speed and the forcing frequency increase. However, this reduction in maximum displacement is accompanying with increasing in the steady state vibration displacement. It is also indicated that the energy dissipation in moving absorber covers higher range of frequencies.

Keywords: absorber performance, Aeolian vibration, Hamilton’s principle, stockbridge damper

Procedia PDF Downloads 231