High-Frequency Spectrum Analysis of VFTO Generated inside Gas Insulated Substations
Commenced in January 2007
Frequency: Monthly
Edition: International
Paper Count: 33122
High-Frequency Spectrum Analysis of VFTO Generated inside Gas Insulated Substations

Authors: M. A. Abd-Allah, A. Said, Ebrahim A. Badran

Abstract:

Worldwide many electrical equipment insulation failures have been reported caused by switching operations, while those equipments had previously passed all the standard tests and complied with all quality requirements. The problem is mostly associated with high-frequency overvoltages generated during opening or closing of a switching device. The transients generated during switching operations in a Gas Insulated Substation (GIS) are associated with high frequency components in the order of few tens of MHz. The frequency spectrum of the VFTO generated in the 220/66 kV Wadi-Hoff GIS is analyzed using Fast Fourier Transform technique. The main frequency with high voltage amplitude due to the operation of disconnector (DS5) is 5 to 10 MHz, with the highest amplitude at 9 MHz. The main frequency with high voltage amplitude due to the operation of circuit breaker (CB5) is 1 to 25 MHz, with the highest amplitude at 2 MHz. Mitigating techniques damped the oscillating frequencies effectively. The using of cable terminal reduced the frequency oscillation effectively than that of OHTL terminal. The using of a shunt capacitance results in vanishing the high frequency components. Ferrite rings reduces the high frequency components effectively especially in the range 2 to 7 MHz. The using of RC and RL filters results in vanishing the high frequency components.

Keywords: GIS, VFTO, Mitigation Techniques, Frequency spectrum, FFT, EMTP/ATP.

Digital Object Identifier (DOI): doi.org/10.5281/zenodo.1087237

Procedia APA BibTeX Chicago EndNote Harvard JSON MLA RIS XML ISO 690 PDF Downloads 2532

References:


[1] A. J. Martinez, "Statistics Assessment of Very Fast Transient Overvoltages in Gas Insulated Substations", IEEE Power Engineering Society Summer Meeting 2000; 2: 882–883.
[2] X. Dong, S. Rosado, Y. Liu, N. C. Wang, E. L. Line and T. Y. Guo, "Study of Abnormal Electrical Phenomena Effects on GSU Transformers", IEEE Transactions on Power Delivery July 2003; 18(3): 835.
[3] A. Said, Ebrahim A. Badran and M.A. Abd-Allah, “Mitigation of Very Fast Transient Overvoltages at the More Sensitive Points in Gas Insulated Substation”. International Journal of Electrical and Power Engineering, 6(3): 118-123, 2012.
[4] V. Vinod Kumar, M. Joy Thomas, and M. S. Naidu," Influence of Switching Conditions on the VFTO Magnitudes in a GIS", IEEE Transaction on Power Delivary, VOL. 16, NO. 4, 2001.
[5] M. Mohana Rao, M. Joy Thomas, and B. P. Singh," Electromagnetic Field Emission From Gas-to-Air Bushing in a GIS During Switching Operations", IEEE Transactions on Eelectromagnetic Compatipility, VOL. 49, NO. 2, 2007.
[6] M.Mohana Rao MJoy Thomas and B.P.Singh,’’ Frequency spectrum analysis of fast transient currents (FTC) due to switching operations in a 245 kV GIS ‘’, Asia Pacific. IEEE/PES, Transmission and Distribution Conference and Exhibition , 2239 – 2243, vol.3, 6-10 Oct. 2002.
[7] Wan Yiru, Chen Guang and Zhou Hao,” Study on VFTO in UHV GIS Substation” 4th International Conference on Electric Utility Deregulation and Restructuring and Power Technologies (DRPT), 2011.
[8] Ahmad Tavakoli, Ahmad Gholami," Influence of Terminal Components for Suppression of High-Frequency Transients in GIS", International Power and Energy Conference (IPEC 2010), Singapore, 27-29 Oct. 2010.
[9] Fan Li-ping and Liang Yu,” The Effect of Appartus Model on Very Fast Transient Over-voltage”, International Conference on Electric Information and Control Engineering (ICEICE),15-17 April, 2011.
[10] L. Qingmin and W Minglei, "Simulation Method for the Applications of Ferromagnetic Materials in Suppressing High Frequency Transients Within GIS". IEEE Transactions on Power Delivery July 2007; 22(3): 1628.
[11] Mariusz Stosur, Marcin Szewczyk, Wojciech Piasecki,Marek Florkowski and Marek Fulczyk ," GIS Disconnector Switching Operation– VFTO Study", Modern Electric Power Systems 2010, MEPS'10 - paper 13.4, Wroclaw, Poland.
[12] J. V. G. Rama Rao, J. Amarnath and S. Kamakshaiah, "Accurate Modeling of Very Fast Transients Overvoltages in A 245kVGIS and Research on Protection Measures", IEEE International conference on Electrical Insulation and Dielectric phenomena((CEIDP2010), West Lafayette, USA.
[13] Wang Zhuo, Wang Weiquan and Wang Qiang, "Research of Suppressing VFTO for 500kV GIS Substation Based on EMTP/ATP", International Conference on E -Business and E -Government (ICEE), 6- 8 May 2011.
[14] J. V. G. Rama Rao, J. Amarnath and S. Kamakshaiah, " Time-Frequency Analysis Of Very Fast Transient Over Voltages For Effective Shielding Of Control Circuits In A 245kv Gas Insulated Substation", International conference on High Voltage Engineering and Application (ICHVE), 11- 14 Oct, 2010.