Permanent Reduction of Arc Flash Energy to Safe Limit on Line Side of 480 Volt Switchgear Incomer Breaker
Commenced in January 2007
Frequency: Monthly
Edition: International
Paper Count: 33122
Permanent Reduction of Arc Flash Energy to Safe Limit on Line Side of 480 Volt Switchgear Incomer Breaker

Authors: Md Abid Khan

Abstract:

A recognized engineering challenge is related to personnel protection from fatal arc flash incident energy in the line side of the 480-volt switchgears incomer breakers during maintenance activities. The incident energy is typically high due to slow fault clearance and it can be higher than the available personnel protective equipment (PPE) ratings. A fault on the line side of the 480 Volt breaker is cleared by breakers or fuses in the upstream higher voltage system (4160 Volt or higher). The current reflection in the higher voltage upstream system for a fault in the 480-volt switchgear is low, the clearance time is slower and the inversely proportional incident energy is hence higher. The installation of overcurrent protection at 480-volt system upstream of the incomer breaker will operate fast enough and trips the upstream higher voltage breaker when a fault develops at the incomer breaker. Therefore, fault current reduction as reflected in the upstream higher voltage system is eliminated. Since the fast overcurrent protection is permanently installed, it is always functional, do not require human interventions and eliminates exposure to human errors. It is installed at the maintenance activity location and its operations can be locally monitored by craftsmen during maintenance activities.

Keywords: Arc flash, mitigation, maintenance switch, energy level.

Procedia APA BibTeX Chicago EndNote Harvard JSON MLA RIS XML ISO 690 PDF Downloads 510

References:


[1] Daleep Mohla, Jim Phillips, “IEEE Standard 1584” (IEEE guide for performing Arc Flash hazard Calculations), 2021, pp. 20-22, 40 and 34-43.
[2] NFPA-70E (National Fire Protection Association), 2018, pp. 15, 24-29 and 32-37.
[3] Wallace S. Read, Donald C. Loughry, “ANSI/IEEE Std 141” (IEEE Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems), 1993, pp. 186.
[4] Donald C. Loughry, Richard J. Holleman, “IEEE Std. 399” (IEEE Recommended Practice for Industrial and Commercial Power System Analysis), 1998, pp.429.
[5] Donald N. Heirman, James T. Cario, “ANSI/IEEE Std 242” (IEEE Recommended Practice for Protection and Coordination of Industrial and Commercial), 2001, pp.26.