A Novel Solution to Restricted Earth Fault Low Impedance Relay Maloperation
Commenced in January 2007
Frequency: Monthly
Edition: International
Paper Count: 33122
A Novel Solution to Restricted Earth Fault Low Impedance Relay Maloperation

Authors: K. N. Dinesh Babu, R. Ramaprabha, V. Rajini, V. Nagarajan

Abstract:

In this paper, various methods of providing restricted earth fault protection are discussed. The proper operation of high and low impedance Restricted Earth Fault (REF) protection for various applications has been discussed. The maloperation of a relay due to improper placement of CTs has been identified and a simple/unique solution has been proposed in this work with a case study. Moreover, it is found that the proper placement of CT in high impedance method will provide the same result with reduced CT. This methodology has been successfully implemented in Al Takreer refinery for a 2000 KVA transformer. The outcome of the paper may be included in IEEEC37.91 standard to give the proper guidance for protection engineers to sort out the issues related to mal functioning of REF relays.

Keywords: Relay maloperation, transformer, low impedance REF, MatLab, 64R, IEEE C37.91.

Digital Object Identifier (DOI): doi.org/10.5281/zenodo.1109425

Procedia APA BibTeX Chicago EndNote Harvard JSON MLA RIS XML ISO 690 PDF Downloads 3930

References:


[1] V K Metha & Rohit Metha, Principles of power system, ISBN:81-219- 2496-0.
[2] Sunil S Rao, Switchgear and protection, Khanna publishers, fourth reprint, 1996.
[3] T60 transformer protection system, UR series instruction annual, version 7.2x, Manual P/N:1601-0090-AA1 (GEK-119568)
[4] High impedance restricted earth fault protection, technical guidance notes, SIEMENS.
[5] IEEE guide for protective relay applications to power transformers, C37.91-2000