Abstract:
In this paper, monitoring and control of tap changer mechanism of a transformer implementation in an Intelligent Electronic Device (IED) is discussed. It has been a custom for decades to provide a separate panel for on load tap changer control for monitoring the tap position. However, this facility cannot either record or transfer the information to remote control centers. As there is a technology shift towards the smart grid protection and control standards, the need for implementing remote control and monitoring has necessitated the implementation of this feature in numerical relays. This paper deals with the programming, settings and logic implementation which is applicable to both IEC 61850 compatible and non-compatible IEDs thereby eliminating the need for separate tap changer control equipment. The monitoring mechanism has been implemented in a 28MVA, 110 /6.9kV transformer with 16 tap position with GE make T60 IED at Ultratech cement limited Gulbarga, Karnataka and is in successful service.Keywords: Transformer protection, tap changer control, tap position monitoring, on load tap changer, intelligent electronic device (IED).
Digital Object Identifier (DOI): doi.org/10.5281/zenodo.1108492
Procedia APA BibTeX Chicago EndNote Harvard JSON MLA RIS XML ISO 690 PDF Downloads 4031References:
[1] Dr Dieter dohnal, “On-load tap changers for power transformers”, MR Knowledge base.
[2] IEEE Std C57.131–2012, IEEE Standard Requirements for Tap- Changers
[3] VR 402 data sheet, Tillquist
[4] www.gedigitalenergy.com
[5] T60 Transformer protection system, UR series instruction manual, Manual P/N:1601-0090-AA1 (GEK-119568)
[6] IEEE C37.2, “IEEE Standard for electrical power system device function numbers, acronyms, and contact designations”.
[7] Nelli Sichwart, Thesis on ‘Transformer load tap changer control using IEC 61850 GOOSE messaging’, Univerisity of Tennessee at Chattanooga.
[8] Zoran Gajic and Samir Aganovic, ‘Advanced tapchanger control to counteract power system voltage instability’, ABB application notes.
[9] E TOM Jauch, ‘Advanced transformer paralleling’, beckwithelectric application notes.
[10] On-load tap-changers, type UZ user’s manual, ABB, 1ZSE 5492-154 en, Rev.4
[11] Multisync 100 GPS clock brochure, GEA-12796(E)