2 Diagnostic of Breakdown in High Voltage Bushing Power Transformer 500 kV Cirata Substation

Authors: Andika Bagaskara, Andhika Rizki Pratama, Lalu Arya Repatmaja, Septhian Ditaputra Raharja

Abstract:

The power transformer is one of the critical things in system transmission. Regular testing of the power transformer is very important to maintain the reliability of the power. One of the causes of the failure of the transformer is the breakdown of insulation caused by the presence of voids in the equipment that is electrified. As a result of the voids that occur in this power transformer equipment, it can cause partial discharge. Several methods were used to determine the occurrence of damage to the power transformer equipment, such as Sweep Frequency Response Analysis (SFRA) and Tan Delta. In Inter Bus Transformer (IBT) 500/150 kV Cirata Extra High Voltage (EHV) Substation, a breakdown occurred in the T-phase tertiary bushing. From the lessons learned in this case, a complete electrical test was carried out. From the results of the complete electrical test, there was a suspicion of deterioration in the post-breakdown SFRA results. After overhaul and inspection, traces of voids were found on the tertiary bushing, which indicated a breakdown in the tertiary bushing of the IBT 500/150kV Cirata Substation transformer.

Keywords: void, bushing, SFRA, Tan Delta

Procedia PDF Downloads 91
1 Effect of Slope Steepness with Toposequent on Erosion Factor: A Study Case of Cikeruh Catchment Area, West Java, Indonesia

Authors: Shantosa Yudha Siswanto, Julianto Arief Ismail, Rachmat Harryanto

Abstract:

The research was conducted with the aim to know the effect of slope steepness on organic carbon and soil erodibility as erosion factor. This research was conducted from September to December 2011 in the Raharja and Cinanjung Village, Tanjungsari, Sumedang District, West Java, Indonesia. The study was carried out using physiographic free survey method, which is a survey based on land physiographic appearance. Soil sampling was carried out into transect on the similarity slope without calculating the point of observation range. Soil sampling was carried onto three classes of slope as follows: 8–15%, 15–25% and 25–40%. Each was consisted of three slope position i.e. top slope, middle slope and down slope and four samples of soil were taken from each of them, hence it resulted in 36 points of observation. The results of this study indicate that gradient of slope have some significant contribution in every sample. Middle slope with gradient 26-40% has the highest potential erosion occurrence. It has organic C content (0.84%) and the highest erodibility value (0.1092).

Keywords: slope steepness, erosion, erodibility, erosion factor

Procedia PDF Downloads 370