2 Temperature Investigations in Two Type of Crimped Connection Using Experimental Determinations
Authors: C. F. Ocoleanu, A. I. Dolan, G. Cividjian, S. Teodorescu
Abstract:
In this paper we make a temperature investigations in two type of superposed crimped connections using experimental determinations. All the samples use 8 copper wire 7.1 x 3 mm2 crimped by two methods: the first method uses one crimp indents and the second is a proposed method with two crimp indents. The ferrule is a parallel one. We study the influence of number and position of crimp indents. The samples are heated in A.C. current at different current values until steady state heating regime. After obtaining of temperature values, we compare them and present the conclusion.Keywords: crimped connections, experimental determinations, temperature, heat transfer
Procedia PDF Downloads 2691 Solutions for Quality Pre-Control of Crimp Contacts
Authors: C. F. Ocoleanu, G. Cividjian, Gh. Manolea
Abstract:
In this paper, we present two solutions for connections quality pre-control of Crimp Contacts and to identify in the first moments the connections improperly executed, before final assembly of a electrical machines. The first solution supposed experimental determination of specific losses by calculated the initial rate of temperature rise. This can be made drawing the tangent at the origin at heating curve. The method can be used to identify bad connections by passing a current through the winding at ambient temperature and simultaneously record connections temperatures in the first few minutes since the current is setting. The second proposed solution is to apply to each element crimping a thermal indicator one level, and making a test heating with a heating current corresponding to critical temperature indicator.Keywords: temperature, crimp contact, thermal indicator, current distribution, specific losses
Procedia PDF Downloads 421