	  abstract     = {Power transformer consists of components which are
under consistent thermal and electrical stresses. The major
component which degrades under these stresses is the paper
insulation of the power transformer. At site, lightning impulses and
cable faults may cause the winding deformation. In addition, the
winding may deform due to impact during transportation. A
deformed winding will excite more stress to its insulating paper thus
will degrade it. Insulation degradation will shorten the life-span of
the transformer. Currently there are two methods of detecting the
winding deformation which are Sweep Frequency Response
Analysis (SFRA) and Low Voltage Impulse Test (LVI). The latter
injects current pulses to the winding and capture the admittance
plot. In this paper, a transformer which experienced overheating and
arcing was identified, and both SFRA and LVI were performed.
Next, the transformer was brought to the factory for untanking. The
untanking results revealed that the LVI is more accurate than the
SFRA method for this case study.},
	    journal   = {International Journal of Mechanical and Mechatronics Engineering},
	  volume    = {4},
	  number    = {12},
	  year      = {2010},
	  pages     = {1430 - 1435},
	  ee        = {https://publications.waset.org/pdf/5764},
	  url   	= {https://publications.waset.org/vol/48},
	  bibsource = {https://publications.waset.org/},
	  issn  	= {eISSN: 1307-6892},
	  publisher = {World Academy of Science, Engineering and Technology},
	  index 	= {Open Science Index 48, 2010},
	}