F. N. Budiman and Y. Khan and A. A. Khan and A. Beroual and N. H. Malik and A. A. Al-Arainy
Dependence of Particle Initiated PD Characteristics on Size and Position of Metallic Particle Adhering to the Spacer Surface in GIS
349 - 353
2013
7
3
International Journal of Electrical and Computer Engineering
https://publications.waset.org/pdf/14800
https://publications.waset.org/vol/75
World Academy of Science, Engineering and Technology
It is well known that metallic particles reduce the
reliability of GasInsulated Substation (GIS) equipments by initiating
partial discharge (PDs) that can lead to breakdown and complete
failure of GIS. This paper investigates the characteristics of PDs
caused by metallic particle adhering to the solid spacer. The PD
detection and measurement were carried out by using IEC 60270
method with particles of different sizes and at different positions on
the spacer surface. The results show that a particle of certain size at
certain position possesses a unique PD characteristic as compared to
those caused by particles of different sizes andor at different
positions. Therefore PD characteristics may be useful for the particle
size and position identification.
Open Science Index 75, 2013