Three Phase Fault Analysis of DC-Link Rectifier using new Power Differential Protection Concept
Commenced in January 2007
Frequency: Monthly
Edition: International
Paper Count: 32807
Three Phase Fault Analysis of DC-Link Rectifier using new Power Differential Protection Concept

Authors: A. Gamil, G. Herold

Abstract:

The concept of differential protection based on current quantities has been discussed in many paper and researches. For certificating and inverting of currents and voltages through converter systems, there is no conventional current differential relay, which can compare current quantities, because they are different in form and frequencies. An overview over a new concept of differential protection for converters based on instantaneous power quantities will be discussed in this paper. To drive the power quantities a mathematical background of the space vectors will be introduced. A simple DCLink is preceded in this paper and a power analysis description and simulation is derived using Matlab®/ SimulinkTM concerning a certain construction scheme of Power Differential Relay System. Finally a complete analysis of three phase fault in DC-Link Rectifier is discussed to ensure the ability of Power Differential Protection System to detect the fault in main and selectivity protection sections.

Keywords: Space Vectors, Power Differential Relay (PDR), Short Circuit Power, Diode Recovery Energy, Detected Power Differential Signal (DPDS), Power Space Vector (PSV), Power Space Vector Protection Area (PSVPA).

Digital Object Identifier (DOI): doi.org/10.5281/zenodo.1079810

Procedia APA BibTeX Chicago EndNote Harvard JSON MLA RIS XML ISO 690 PDF Downloads 3349

References:


[1] G. Herold, Elektrische Energieversorgung I, Schlem- bach Fachverlag, 2002.
[2] M. Schuster, Vergleichschutz auf Leistungsbasis, Doctor Thesis, 2000.
[3] T. Gönen, Electric Power Transmission System Engineering, John Wiley & Sons, 1988.
[4] G. Ziegler, Digital Differential Protection, Siemens, 2004.
[5] Seiver & Paschal, Short Circuit Calculations "The Easy Way", A Primedia Company, Kansas, 1999.
[6] D. A. Woodford, HVDC Transmission, Manitoba HVDC Research Center, Canada, 1998.
[7] L. M. Tolbert, Compensation Based Non Active Power Definition, IEEE Power Electronics Letters, Vol.1 No.2, 2003.
[8] T. Hayder, Schutz von Regeltransformatoren, Doctor Thesis, 2006.
[9] A. Krasovec, Turn-to-Turn Fault in Single-Phase Power Transformers, PSP 2002, p. 83-86.
[10] URL: http://ocw.mit.edu/NR/rdonlyres/Electrical-Engineering-and- Computer-Science/6-720JIntegrated-Microelectronic- DevicesFall2002/1D397531-06EE-452E-B2D3- E8EF7F19DB59/0/lecture19.pdf