	%X This paper presents the experimental as well as the
simulated performance studies on the transcritical CO2 heat pumps
for simultaneous water cooling and heating; effects of water mass
flow rates and water inlet temperatures of both evaporator and gas
cooler on the cooling and heating capacities, system COP and water
outlets temperatures are investigated. Study shows that both the
water mass flow rate and inlet temperature have significant effect on
system performances. Test results show that the effect of evaporator
water mass flow rate on the system performances and water outlet
temperatures is more pronounced (COP increases 0.6 for 1 kg/min)
compared to the gas cooler water mass flow rate (COP increases 0.4
for 1 kg/min) and the effect of gas cooler water inlet temperature is
more significant (COP decreases 0.48 for given ranges) compared to
the evaporator water inlet temperature (COP increases 0.43 for given
ranges). Comparisons of experimental values with simulated results
show the maximum deviation of 5% for cooling capacity, 10% for
heating capacity, 16% for system COP. This study offers useful
guidelines for selecting appropriate water mass flow rate to obtain
required system performance.
	%P 571 - 577