WASET
	%0 Journal Article
	%A Ahmet Y. Arabul and  Ibrahim Senol and  Fatma Keskin Arabul and  Mustafa G. Aydeniz and  Yasemin Oner and  Gokhan Kalkan
	%D 2015
	%J International Journal of Energy and Power Engineering
	%B World Academy of Science, Engineering and Technology
	%I Open Science Index 104, 2015
	%T An Investigation on Hot-Spot Temperature Calculation Methods of Power Transformers
	%U https://publications.waset.org/pdf/10003802
	%V 104
	%X In the standards of IEC 60076-2 and IEC 60076-7, three different hot-spot temperature estimation methods are suggested. In this study, the algorithms which used in hot-spot temperature calculations are analyzed by comparing the algorithms with the results of an experimental set-up made by a Transformer Monitoring System (TMS) in use. In tested system, TMS uses only top oil temperature and load ratio for hot-spot temperature calculation. And also, it uses some constants from standards which are on agreed statements tables. During the tests, it came out that hot-spot temperature calculation method is just making a simple calculation and not uses significant all other variables that could affect the hot-spot temperature.

	%P 1036 - 1040