	  abstract     = {Since large power transformers are the most
expensive and strategically important components of any power
generator and transmission system, their reliability is crucially
important for the energy system operation. Also, Circuit breakers are
very important elements in the power transmission line so monitoring
the events gives a knowledgebase to determine time to the next
maintenance. This paper deals with the introduction of the
comparative method of the state estimation of transformers and
Circuit breakers using continuous monitoring of voltage, current.
This paper gives details a new method based on wavelet to apparatus
insulation monitoring. In this paper to insulation monitoring of
transformer, a new method based on wavelet transformation and
neutral point analysis is proposed. Using the EMTP tools, fault in
transformer winding and the detailed transformer winding model
were simulated. The current of neutral point of winding was analyzed
by wavelet transformation. It is shown that the neutral current of the
transformer winding has useful information about fault in insulation
of the transformer.},
	    journal   = {International Journal of Electrical and Computer Engineering},
	  volume    = {4},
	  number    = {10},
	  year      = {2010},
	  pages     = {1548 - 1552},
	  ee        = {https://publications.waset.org/pdf/4360},
	  url   	= {https://publications.waset.org/vol/46},
	  bibsource = {https://publications.waset.org/},
	  issn  	= {eISSN: 1307-6892},
	  publisher = {World Academy of Science, Engineering and Technology},
	  index 	= {Open Science Index 46, 2010},
	}