	%X This paper presents the experimental results of
discharge current phenomena on various humidity, temperature,
pressure and pollutant conditions of epoxy resin specimen. The
leakage distance of specimen was 3 cm, that it was supplied by high
voltage. The polluted condition was given with NaCl artificial
pollutant. The conducted measurements were discharge current and
applied voltage. The specimen was put in a hermetically sealed
chamber, and the current waveforms were analyzed with FFT.
The result indicated that on discharge condition, the fifth
harmonics still had dominant, rather than third one. The third
harmonics tent to be appeared on low pressure heavily polluted
condition, and followed by high humidity heavily polluted condition.
On the heavily polluted specimen, the peaks discharge current points
would be high and more frequent. Nevertheless, the specimen still
had capacitive property. Besides that, usually discharge current
points were more frequent. The influence of low pressure was still
dominant to be easier to discharge. The non-linear property would be
appear explicitly on low pressure and heavily polluted condition.
	%P 2212 - 2221