	%X This paper presents the development of adaptive
distance relay for protection of parallel transmission line with mutual
coupling. The proposed adaptive relay, automatically adjusts its
operation based on the acquisition of the data from distance relay of
adjacent line and status of adjacent line from line circuit breaker IED
(Intelligent Electronic Device). The zero sequence current of the
adjacent parallel transmission line is used to compute zero sequence
current ratio and the mutual coupling effect is fully compensated.
The relay adapts to changing circumstances, like failure in
communication from other relays and non - availability of adjacent
transmission line. The performance of the proposed adaptive relay is
tested using steady state and dynamic test procedures. The fault
transients are obtained by simulating a realistic parallel transmission
line system with mutual coupling effect in PSCAD. The evaluation
test results show the efficacy of adaptive distance relay over the
conventional distance relay.