	%T Study on Using the Ground as A Heat Sink for A 12,000-Btu/h Modified Air Conditioner
	%U https://publications.waset.org/pdf/2605
	%V 27
	%X This paper presents the results of the experimental
tests of the cooling performance of a 12,000-Btu/h modified air
conditioner (referred to as M-AC) that use the ground as a heat sink
of a condenser. In the tests, cooling capacity of M-AC with an
optimal length of a condensing coil as well as life expectancy of
copper coil buried underground were investigated. The lengths of
copper coil fabricated and used as condenser coil of M-AC were set
at 67, 50, 40 and 30 m whereas that of a 12,000-Btu/h conventional
split-type air conditioner (referred to as C-AC) was about 22 m. The
results showed that the ground can absorb heat rejected from a
condenser of M-AC. The coefficient of performance (COP) of C-AC
was about 2.5 whereas those of M-AC were found to be higher. It
was found that the values of COP of M-AC with condensing coils of
67, 50 and 40 m long were about 6.9, 5.5 and 3.3, respectively, while
that of 30-m-long one was found to be about 2.1. The electrical
consumptions of M-AC were found lower than that of C-AC in the
range of 11.5 – 15.5%. Additionally, life expectancy of underground
condensing coil of M-AC was found to be over 7 years.
	%P 120 - 123