Investigation of SSR Characteristics of SSSC With GA Based Voltage Controller
Commenced in January 2007
Frequency: Monthly
Edition: International
Paper Count: 32797
Investigation of SSR Characteristics of SSSC With GA Based Voltage Controller

Authors: R. Thirumalaivasan, M.Janaki, Nagesh Prabhu

Abstract:

In this paper, investigation of subsynchronous resonance (SSR) characteristics of a hybrid series compensated system and the design of voltage controller for three level 24-pulse Voltage Source Converter based Static Synchronous Series Compensator (SSSC) is presented. Hybrid compensation consists of series fixed capacitor and SSSC which is a active series FACTS controller. The design of voltage controller for SSSC is based on damping torque analysis, and Genetic Algorithm (GA) is adopted for tuning the controller parameters. The SSR Characteristics of SSSC with constant reactive voltage control modes has been investigated. The results show that the constant reactive voltage control of SSSC has the effect of reducing the electrical resonance frequency, which detunes the SSR.The analysis of SSR with SSSC is carried out based on frequency domain method, eigenvalue analysis and transient simulation. While the eigenvalue and damping torque analysis are based on D-Q model of SSSC, the transient simulation considers both D-Q and detailed three phase nonlinear system model using switching functions.

Keywords: FACTS, SSR, SSSC, damping torque, GA.

Digital Object Identifier (DOI): doi.org/10.5281/zenodo.1056202

Procedia APA BibTeX Chicago EndNote Harvard JSON MLA RIS XML ISO 690 PDF Downloads 1675

References:


[1] N. G. Hingorani and L. Gyugyi, Understanding FACTS, New York: IEEE Press, 2000.
[2] K. R. Padiyar, Analysis of Subsynchronous Resonance in power systems, Boston: Kluwer Academic Publishers,1999.
[3] K. R. padiyar and Nagesh prabhu, .Analysis of SSR with three level Twelve-pulse VSC based Interline Power flow Controller., IEEE Trans.Power Delivery., Vol.22, No.3, pp. 1688-1695, July 2007.
[4] R. W. Menzis and Yiping Zhuang, .Advanced static compensation using a multilevel GTO thyristor inverter,. IEEE Transactions on Power Delivery, Vol.10, No.2, April 1995.
[5] J. B. Ekanayake and N. Jenkins, .Mathematical models of a three level advanced static var compensator,. IEE Proc.- Generation Transm distrib, vol. 144, No.2, March 1997.
[6] K. K. Sen and E. J. Stacy, .UPFC- Unified Power Flow Controller: Theory, Modelling and Applications., IEEE Trans. Power Del., Vol.13, No.4, pp. 1453-1460, October 1998.
[7] K. R. Padiyar, FACTS Controllers in Power transmission and Distribution, New Delhi: New Age international (P) Limited, 2007.
[8] Schauder and Mehta, .Vector analysis and control of advanced static VAR compensators,. IEE Proc.-c, vol. 140, no. 4, pp. 299-306, July 1993.
[9] K. R. Padiyar and N. Prabhu, "Analysis of subsynchronous resonance with three level twelve-pulse VSC based SSSC," in Proc. IEEE TENCON-2003, Oct. 14-17, 2003.
[10] Nagesh Prabhu, "Analysis of SubSynchronous Resonance with Voltage Source Converter based FACTS and HVDC Controllers," Ph.D. dissertation, IISc Bangalore, 2004.
[11] K. R. Padiyar, Power System Dynamics - Stability and Control- Second edition, Hyderabad: B.S.Publications, 2002.
[12] I. M. Canay, .A Novel Approach to the Torsional Interactions and Electrical Damping of the Synchronous Machine, Part-I: Theory, Part-II: Application to an arbitrary network., IEEE Trans. Power App. and Syst.,vol. PAS-101, No.10, pp. 3630-3647, 1982.
[13] IEEE committee report, "First bench mark model for computer simulation of subsynchronous resonance"," IEEE Trans. Power App. Syst., vol. PAS-96, pp. 1565-1572, Sep./Oct. 1977.
[14] The Math works Inc, .Using MATLAB-SIMULINK., 1999.
[15] Goldberg, "Genetic Algorithm In search, Optimization and Machine Learning", Addison Wesley Reading, 1989.
[16] K. R. padiyar and Nagesh Prabhu, "Design and Performance Evalution of Subsynchronous Damping Controller with STATCOM", IEEE Trans. On Power Delivery, vol.21, No.3, July 2006.
[17] Nagesh Prabhu and K. R. padiyar, .Investigation of Subsynchronous Resonance with VSC based HVDC Transmission Systems., To appear in IEEE Trans. Power Delivery.,TPWRD-00654-2007.R2, 2008.