WASET
	%0 Journal Article
	%A K. Pana-Suppamassadu and  P. Jeimrittiwong and  P. Narataruksa and  S. Tungkamani
	%D 2009
	%J International Journal of Chemical and Molecular Engineering
	%B World Academy of Science, Engineering and Technology
	%I Open Science Index 29, 2009
	%T Effects of Operating Conditions on Calcium Carbonate Fouling in a Plate Heat Exchanger
	%U https://publications.waset.org/pdf/1090
	%V 29
	%X The aim of this work is to investigate on the internalflow
patterns in a plate heat exchanger channel, which affect the
rate of sedimentation fouling on the heat transfer surface of the
plate heat exchanger. The research methodologies were the
computer simulation using Computational Fluid Dynamics (CFD)
and the experimental works. COMSOL MULTIPHYSICS™
Version 3.3 was used to simulate the velocity flow fields to verify
the low and high flow regions. The results from the CFD technique
were then compared with the images obtained from the
experiments in which the fouling test rig was set up with a singlechannel
plate heat exchanger to monitor the fouling of calcium
carbonate. Two parameters were varied i.e., the crossing angle of
the two plate: 55/55, 10/10, and 55/10 degree, and the fluid flow
rate at the inlet: 0.0566, 0.1132 and 0.1698 m/s. The type of plate
“GX-12" (the surface area 0.12 m2, the depth 2.9 mm, the width of
fluid flow 215 mm and the thickness of stainless plate of 0.5 mm)
was used in this study. The results indicated that the velocity
distribution for the case of 55/55 degree seems to be very well
organized when compared with the others. Also, an increase in the
inlet velocity resulted in the reduction of fouling rate on the surface
of plate heat exchangers.
	%P 276 - 287